Glasgow Electric Plant Board
Rates - Rules & Regulations
ELECTRIC PLANT BOARD
CITY OF GLASGOW
GLASGOW, KENTUCKY
GENERAL SCHEDULE OF RULES AND REGULATIONS
AS APPROVED AND ADOPTED BY THE BOARD OF DIRECTORS ON MARCH
25, 1997
Table of Contents - Quick Index
(Click on an item to jump directly to it)
GLASGOW ELECTRIC PLANT BOARD (GEPB)
UNDERGROUND POLICIES
(effective May 31, 1999)
GLASGOW ELECTRIC PLANT BOARD (GEPB)
POLICY ON UNDERGROUND SERVICES AND FACILITIES
UNDERGROUND SERVICES FROM OVERHEAD PRIMARY
AND TRANSFORMERS
- Customer to contact GEPB Engineering Department for spotting
meter location on building. This meter location will be on the side of the
house closest to existing electrical facilities. It cannot be in a carport,
porch area or wood deck. When the building and lot are such that the total
length of underground conduit shall exceed 200 feet or, if service size exceeds
200 amps, these specifications and requirements may be altered and a custom
arrangement may be specified by GEPB. Exact location of meter, conduits and
riser elbows must be approved by GEPB Engineering Department prior to installation.
- Customer to open trench from meter location to pole. Minimum
depth of conduit to be 24 inches below existing and finished grade including
drainage ditches. Installation must be approved by GEPB Engineering Department
before trench is backfilled. Please give at least one day advance notification.
Trench must be backfilled before electrical conductor can be installed.
- When a straight run of conduit is all that is required, Customer
shall furnish and install two continuous runs of conduit to include one minimum
size of 2 1/2" I.D. and one 2" I.D., each terminated with two 90º 18"
radius elbows. All conduit and fittings shall be Schedule 40 electrical grade
PVC. Exception: All conduit beneath road surfaces shall be Schedule 80 electrical
grade or approved equal.
- When other than a straight run of conduit is required, then
the customer is to furnish and install two continuous runs of conduit to include
one minimum size of 2 1/2" I.D. and one 2" I.D., each with no more than three
90º 18" radius elbows. Two 45º 18" radius bends separated by at
least 20 feet of straight conduit may be substituted for mid-run 90º
18" elbow. Any other arrangement of conduits must be approved prior to installation
by GEPB Engineering Department.
- Conduits shall be capped at exposed ends. A pull string is
to be provided in place for use in pulling the cable through each conduit.
This string shall be rated at least 150 lbs. and be nylon construction.
- Trench to be backfilled with clean dirt and NO foreign material
or building debris is allowed in the ditch.
- Top of meter socket is to be located at a height of 6 feet
above finished grade so that meter is eye-level. A suitable expansion coupling
shall be installed at the meter base.
- Ground rods to be provided and installed by customer. Each
ground rod is to be eight feet in length. Ground in accordance with the National
Electrical Code and the City Ordinance. More than one ground rod may be required.
All grounds must be connected together.
- If an existing customer requests underground service for
his own convenience, the customer shall install the conduit to required underground
standards. GEPB will install new underground service conductor and remove
overhead service conductor at a cost of $150.00. Special circumstances may
necessitate additional charges.
Approved by Board of Directors
March 23, 1999
GLASGOW ELECTRIC PLANT BOARD (GEPB)
POLICY ON UNDERGROUND SERVICES AND FACILITIES
UNDERGROUND SERVICES FROM UNDERGROUND PADMOUNTED
TRANSFORMERS AND SECONDARY PEDESTALS
- Customer to contact GEPB Engineering Department for spotting
meter location on building. This meter location will be on the side of the
house closest to existing electrical facilities. It cannot be in a carport,
porch area or wood deck. When the building and lot are such that the total
length of underground conduit shall exceed 200 feet or, if service size exceeds
200 amps, these specifications and requirements may be altered and a custom
arrangement may be specified by GEPB. Exact location of meter, conduits, and
riser elbows must be approved by GEPB Engineering Department prior to installation.
- Customer to open trench from meter location to padmount transformer
or service pedestal. Minimum depth of conduit to be 24 inches below existing
and finished grade including drainage ditches. Installation must be approved
by GEPB Engineering Department before trench is backfilled. Please give at
least one day notification. Trench must be backfilled before electrical conductor
can be installed.
- When a straight run of conduit is all that is required, Customer
shall furnish and install two continuous runs of conduit to include one minimum
size of 2 1/2" I.D. and one 2" I.D., each terminated with two 90º 18"
radius elbows, or capped in trench (as required). Customer shall stop ditch
one foot from utility closest to transfomer. All conduit and fittings shall
be Schedule 40 electrical grade PVC. Exception: All conduit beneath road surfaces
shall be Schedule 80 electrical grade or approved equal.
- When other than a straight run of conduit is required, then
the customer is to furnish and install two continuous runs of conduit to include
one minimum size of 2 1/2" I.D. and one 2" I.D. each with no more than three
90º 18" radius elbows. Two 45º 18" radius bends separated by at
least 20 feet of straight conduit may be substituted for mid-run 90º
18" elbow. Any other arrangement of conduits must be approved prior to installation
by GEPB Engineering Department.
- Conduits shall be capped at exposed ends. A pull string is
to be provided in place for use in pulling the cable through the conduit.
This string shall be rated at least 150 lbs. and be nylon construction.
- Trench to be backfilled with clean dirt and NO foreign material
or building debris is allowed in the ditch.
- Top of meter socket is to be located at a height of 6 feet
above finished grade so that meter is eye-level. A suitable expansion coupling
shall be installed at the meter base.
- Ground rods to be provided and installed by customer. Each
ground rod is to be eight feet in length. Ground in accordance with the National
Electrical Code and the City Ordinance. More than one ground rod may be required.
All grounds must be connected together.
- All bushes or other obstructions must be no closer than five
feet from any side of padmounted transformer or other type of ground-mounted
equipment. No trees or bushes shall be planted on top of the service. All
bushes, fences, or other obstructions must be no closer than eight feet from
the door or front of ground-mounted equipment.
Approved by Board of Directors
March 23, 1999
GLASGOW ELECTRIC PLANT BOARD (GEPB)
POLICY ON UNDERGROUND SERVICES AND FACILITIES
UNDERGROUND PRIMARY TO SUBDIVISIONS, ETC.
Note: The customer shall submit to GEPB a written request for
electrical service along with a complete plat of the development. This request
and plat shall outline which areas are to be developed first, second, third,
etc., which type housing is proposed, anticipated construction schedules and
proposed locations of all utilities. GEPB will not start any construction until
the plat is recorded and we have written authorization from the Developer. All
significant lot corners and control points must be installed prior to GEPB staking
of proposed trenching or inspection of underground conduit system.
- Customer to open trench for area staked by GEPB Engineering
Department. Depth of trench to finished grade shall be a minimum of 48" for
primary cable.
- All conductor routes, conductors, meters, service wires,
concrete pads, riser poles, service pedestals, and meter locations shall be
designed and located by GEPB. All such facilities shall remain the property
of GEPB.
- Customer to furnish and install up to four continuous runs
of conduit with minimum size of 2" I.D. with placement and fittings as requested
by GEPB's Engineering Department. All conduit shall be Schedule 40 electrical
grade PVC. All 90º elbows shall be steel and have a minimum radius of
36".
- GEPB will furnish and the customer will install "warning
tape" at a depth of one foot from finish grade. The other run of "warning
tape" will be installed one foot above conduit level. GEPB provides the warning
tape upon request at their warehouse location behind 100 Mallory Drive.
- Conduits shall be capped on exposed ends. A pull string is
to be provided in place for use in pulling the cable through each conduit.
This string shall be rated at least 150 lbs.
- Trench to be backfilled with clean dirt and NO foreign material
or building debris is allowed in the ditch.
- When crossing over other utilities' buried lines, GEPB requires
4" concrete encasement around conduit to length of four feet to each side
of buried line being crossed. When crossing under other utilities' buried
lines, there must be a minimum of 2 feet separation.
- The customer shall provide and install all concrete pads
for the placement of power distribution padmount transformers. All concrete
pads shall be constructed to GEPB specifications. All power conductors, transformers
and other related equipment will be provided and installed by GEPB. GEPB will
provide, and the customer will install any secondary and transformer vaults
to GEPB's specifications.
- Any damage caused to GEPB's facilities during construction
periods shall be the responsibility of the customer/developer along with the
expenses incurred restoring proper service. Damage incurred after completion
of construction shall be the responsibility of the person(s) or firm(s) causing
such damage.
- All underground construction by a customer/developer is subject
to inspection by GEPB and must be approved by GEPB prior to the installation
of conductor and transformers. Conduit is to be inspected before backfilling.
Please notify GEPB Engineering Department at least one day prior to need for
inspection.
- Refer to GEPB's operating policies for additional rules and
regulations.
- All conduit beneath road surfaces shall be Schedule 80 or
encased in a 4" concrete envelope and backfilled with #9 crushed stone.
- Transfer of ownership occurs after facilities installed by
the customer/developer are inspected and approved by GEPB Engineering Department.
The customer/developer will be responsible for any violation of Electrical
Codes or GEPB policy at time violation is found.
- The customer agrees to install the conduit, vaults, concrete
pads, and other equipment at no cost to GEPB in exchange for GEPB providing
electrical service.
- No electrical equipment, conduit or wiring is allowed under
any permanent structure.
- The customer is responsible for correcting any violation
at the time the violation becomes apparent. For example, if the customer should
perform grading work and causes GEPB to no longer meet proper minimum depth,
then the customer must correct the problem to GEPB's specifications.
Approved by Board of Directors
March 23, 1999